7.7
Set values for monitoring the winding temperature
Prior to commissioning
Before running the machine for the first time, set the temperature value for shutdown on the
monitoring device.
Table 7-3
Set value for commissioning
Set value
Temperature
Alarm
145° C
Shutting down
155° C
Normal operation
1. Measure the normal operating temperature T
op
at the installation location in ° C.
2. Set the values for shutdown and warning corresponding to the operating temperature T
op
.
Table 7-4
Set values during normal operation
Set value
Temperature for insulation class 180(H), utilization 155(F)
Alarm
T
op
+ 10 K ≤ 145° C
Shutting down
T
op
+ 15 K ≤ 155° C
7.8
Test run
After installation or inspection, carry out a test run:
1. Start up the machine without a load. To do this, close the circuit breaker and do not switch
off prematurely. Check whether it is running smoothly.
Switching the machine off again while it is starting up and still running at slow speed should
be kept to a bare minimum, for example for checking the direction of rotation or for checking
in general.
Allow the machine to run down before switching it on again.
2. If the machine is running smoothly and evenly, switch on the cooling equipment. Continue
to observe the machine for a while in no-load operation.
Start-up
7.7 Set values for monitoring the winding temperature
SIMOTICS FD 1MH1
110
Operating Instructions 08/2017
Summary of Contents for SIMOTICS FD 1LL1
Page 2: ...18 08 2017 17 24 V10 00 ...
Page 176: ...Disposal 11 4 Disposal of components SIMOTICS FD 1MH1 176 Operating Instructions 08 2017 ...
Page 178: ...Service and Support SIMOTICS FD 1MH1 178 Operating Instructions 08 2017 ...
Page 182: ...Quality documents SIMOTICS FD 1MH1 182 Operating Instructions 08 2017 ...
Page 187: ......