4.19
Converter operation
The following chapter is relevant only if the machine has been ordered for converter operation.
Note
The order number shows whether the machine was ordered for converter operation. In this
case, digits 1, 2, 3 or 4 is located at the 6th position of the order number.
4.19.1
Converter operation of explosion-proof machines
The operation of the explosion-proof machine on the frequency converter is permitted, when
the specifications for the speed control range and torque characteristic are observed, and if
winding temperature monitoring is ensured via the integrated temperature sensors in
conjunction with a tripping unit.
WARNING
Operation with a converter that is not permissible for the application
If a certain converter type has been defined in the test verification document, on the extra
rating plate, or in the certificate, the machine is only allowed to be operated with this converter.
Death, serious injury, or material damage can result if it is operated with an unauthorized
converter.
● Only operate the motor with the specified converter.
4.19.2
Supply line configuration
NOTICE
Asymmetric voltage load during operation on a TN system in delta connection
An asymmetric voltage load of the machine winding can occur during operation on a TN
system in delta connection with a grounded line conductor. Winding damage can result.
● Do not operate the machine on a TN system with a grounded line conductor.
NOTICE
Ground fault during operation on an IT system
If a ground fault occurs when connected to an IT supply system, the insulation is excessively
stressed. Winding damage can result.
● If possible, complete the process within two hours.
● Rectify the fault cause.
● Deploy a ground fault monitoring.
Preparations for use
4.19 Converter operation
SIMOTICS FD 1MH1
52
Operating Instructions 08/2017
Summary of Contents for SIMOTICS FD 1LL1
Page 2: ...18 08 2017 17 24 V10 00 ...
Page 176: ...Disposal 11 4 Disposal of components SIMOTICS FD 1MH1 176 Operating Instructions 08 2017 ...
Page 178: ...Service and Support SIMOTICS FD 1MH1 178 Operating Instructions 08 2017 ...
Page 182: ...Quality documents SIMOTICS FD 1MH1 182 Operating Instructions 08 2017 ...
Page 187: ......