24
4 Setting Up
Version 1.0 8/00
4.4 Installation
4.4.6 Defining the receiving level of the optical ports
The receiving level of the two optical Ports CH2 and CH 3
can be measured using a conventional voltmeter con-
nected to the measuring sockets. The voltmeter can be
connected and disconnected while the module is in
operation without any interference using 2 mm laboratory
test plugs.
The OLM is protected against short circuits at the measu-
ring sockets, although data transmission may be briefly
disrupted*.
With this
– the incoming optical performance can be documented,
e.g. for later measurements (ageing, damage)
– a good/poor check can be carried out (limit value).
Further information can be found in Appendix 8.4
”Measuring sockets“ p.35.
* Only an ungrounded, high-resistance voltmeter may be
used to take measurements.
The reference potential socket may not be connected to
the OLM housing.
CH 1
System
PROFIBUS OLM
CH 2
CH 3
GND
Receive
Signal
Intensity
CH 2 CH 3
Measuring sockets
Reference potential
Fig. 12: Signaling contact – pin assignment 5-pin terminal block
Pin assignment, 5-pin terminal block:
terminals F1 and F2.
Always ensure that the pins are correctly assigned at
the 5-pin terminal block. Make sure that the connecting
leads of the signaling contacts are adequately insula-
ted, particularly if you are working with voltages greater
than 32 V. Incorrect assignment can lead to destruction
of the module.
L1+ / +24 V
F1
M /
F2
L2+ / +24 V*
Fig. 13: Location of the measuring sockets
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...