32
7 Technical Data
Version 1.0 8/00
OLM Module
P11
G11
G11-1300
P12
G12
G12-1300
G12-EEC
Transmission distance
– with glass fiber
E 10/125
–
–
0 - 15 000 m
2)
(0.5 dB/km)
– with glass fiber
G 50/125
–
0 - 3 000 m
2)
0 - 10 000 m
(860 nm: 3.0 dB/km; 1310 nm: 1.0 dB/km)
– with glass fiber
G 62,5/125
–
0 - 3 000 m
2)
0 - 10 000 m
(860 nm: 3.5 dB/km; 1310 nm: 1.0 dB/km)
– with PCF fiber
S 200/230
Transmitting power ”Reduced“
–
–
–
Transmitting power ”Default“
0 - 400 m
2)
–
–
(660 nm: 10.0 dB/km; 860 nm: 8.0 dB/km)
– with plastic fiber
S 980/1000
Transmitting power ”Reduced“
0 - 50 m
–
–
Transmitting power ”Default“
0 - 80 m
–
–
(0.25 dB/m)
Connector
BFOC/2.5
Electromagnetic compatibility (EMC)
Interference emissions
Limit class B (EN 55022)
Interference immunity against static charges
At shielded socket and housing parts: ±8 kV contact discharge
(EN 61000-4-2)
Immunity against high-frequency interference
– 10 V/m at 80% amplitude modulation with 1 kHz,
–
80 MHz - 1 GHz (EN 61000-4-3)
– 10 V/m at 50% on-period at 900 MHz (ENV 50204)
– 10 V/m at 80% amplitude modulation with 1 kHz,
–
10 kHz - 80 MHz
Immunity against line-conducted disturbance
On power supply lines and shielded
(Burst)
RS 485 bus lines: ±2 kV (EN 61000-4-4)
Immunity against line-conducted disturbance
– On power supply lines: ±1 kV symmetrical
(Surge)
– On shielded RS 485 bus lines: ±2 kV asymmetrical
–
(EN 61000-4-5)
Climatic ambient conditions
Ambient temperature
0 °C to +60 °C (IEC 68-2-1, IEC 68-2-2)
–20 °C to +60 °C at OLM/G12-EEC
1)
(IEC 68-2-1, IEC 68-2-2)
Storage temperature
–40 °C to +70 °C (IEC 68-2-14)
Relative humidity
<95 %, non-condensing (IEC 68-2-30)
100 %, condensing at OLM/G12-EEC
1)
(IEC 68-2-30)
Mechanical ambient conditions
Vibration (during operation)
10 to 58 Hz, 0.075 mm displacement;
58 to 150 Hz, 10 m/s
2
(1 g) acceleration (IEC 68–2–6)
Vibration (during transport)
5 to 9 Hz, 3.5 mm displacement;
9 to 500 Hz, 10 m/s
2
(1 g) acceleration
Protection class
IP 40
Dimensions (W x H x D)
39.5 x 110 x 73.2 mm
Housing material
Die-cast zinc
Weight
approx. 500 g
1) The OLM/G12 can also be supplied in a special design for more severe environmental conditions. This variant is designated the OLM/G12-EEC.
The DIL switches on the OLM/G12-EEC may also only be operated at ambient temperatures between 0°C and + 60°C.
2) The specified distance allowed between two OLMs must not be exceeded regardeless of the optical power budget.
The module does not contain any silicon.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...