Installing LAN Cables
C-8
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
C.4.2
Installation and Grounding of Inactive Metal Parts
Grounding
Connect all inactive metal parts in the immediate vicinity of your automation
components and LAN cables to ground (PE system). This includes all metal parts
of cabinets, machine parts etc. that have no electrical function in the automation
system. Connecting these parts to a uniform system chassis produces a uniform
reference potential for your system and reduces the effects of coupled-in
interference. For detailed information about grounding techniques, refer to the
system manuals of the SIMATIC S7–300 /11/ and S7–400 /12/ programmable
controllers.
C.4.3
Using the Shields of Electrical LAN Cables
Definition
Shielding is a technique used to counteract the effects of magnetic, electrical or
electromagnetic interference fields.
Interference currents on cable shields must be discharged to ground by short,
conductive, large-area connections. To prevent these interference currents
reaching a device or wiring closet, this discharge must take place immediately
before or at the point at which the cable enters the device casing/wiring closet.
Cable Shields
Note the following points about cable shields:
S
Use SIMATIC NET PROFIBUS cables throughout your system. The shields of
these cables have an adequate shield density to meet the legal requirements
regarding noise emission and immunity.
S
Always contact the shields of LAN cables at both ends. The legal requirements
for noise emission and noise immunity in your system (CE marking) can only be
achieved when the shields make contact at both ends.
S
Secure the shield of the LAN cable to the connector casing.
S
If cables are installed permanently, it is advisable to remove the insulation of the
shielded cable and to establish contact on the shield/PE conductor bar.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...