SIMATIC NET PROFIBUS Plastic Fiber Optic
Installation Instructions for Simplex Connectors
Page 9
Fitting Simplex Connectors
Insert the cord into the simplex plug as
far as it will go
Œ
and close the clamp
•
.
Caution: The fiber must extend at least
1.5 mm beyond the end face of the
connector.
Close the clamp until you hear the catch
lock in place.
Repeat the same procedure for the
second cord.
Caution: Do not insert the connector into
a device socket, otherwise the excess
fiber length is liable to damage the
transmitter and receiver elements.
Grinding and Polishing Simplex Connectors
Cut off excessive fiber with scissors
leaving approximately 1.5 mm in length.
Insert the simplex connector into the
polishing holder as far as it will go.
Grind down the excess fiber by
describing a figure-of-eight on polishing
paper (600 grit) on a flat solid surface.
The polishing is completed when the
fiber is flush with the end face of the
connector.
Remove the debris from the polishing
holder and from the end face of the
connector using a clean cloth.
Then polish the end face of the
connector by describing figures-of-eight
on the pink polishing foil (rough side).
Repeat the figure-of-eight movement
approximately 25 times.
Polishing reduces the attenuation by
approximately 2 dB (corresponds to
approximately 10 m cable length). With
short lengths of cable polishing is
unnecessary.
Repeat the procedure with the second
connector and clean the surfaces of the
plug with a clean cloth.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...