Configuration
6.2 Configuration of redundant optical rings
Data rate
a
b
c
12
MBit/s
1)
1651
240
28
6
MBit/s
1)
951
120
24
3
MBit/s
1)
551
60
24
1.5 MBit/s
351
30
24
500
kBit/s
251
10
24
187.5 kBit/s
171
3.75
24
93.75 kBit/s
171
1.875
24
45.45 kBit/s
851
0.909
24
19.2 kBit/s
171
0.384
24
9.6
kBit/s
171
0.192
24
Table 3a: Constants for calculating the slot time at DP standard
(redundant optical ring)
Data rate
a
b
c
12
MBit/s
1)
1651
240
28
6
MBit/s
1)
951
120
24
3
MBit/s
1)
551
60
24
1.5 MBit/s
2011
30
24
500
kBit/s
771
10
24
187.5 kBit/s
771
3.75
24
93.75 kBit/s
451
1.875
24
45.45 kBit/s
851
0.909
24
19.2 kBit/s
181
0.384
24
9.6 kBit/s
171
0.192
24
Table 3b: Constants for calculating the slot time at DP/FMS (”universal“)
and DP with S5 95U (redundant optical ring)
The calculation of the slot time only takes into consideration the optical network and the connection of bus sub-
scribers to the OLM via an RS 485 bus segment with a respctive length of max. 20 m. Longer RS 485 bus segments
must be allowed for by adding them to the Length
OF
.
Note:
When the slot time is configured with a too small value the OLM will, through it’s fault function and fault indications,
indicate such. The System-LED will blink red/green.
1)
Using the OLM/G11-1300 and OLM/G12-1300 at data rates of 12 MBit/s, 6 MBit/s, 3 MBit/s and 1.5 MBit/s the
minimum slot times according to the following table must be met.
Data rate
Minimum slot time
12 MBit/s
3800 t
Bit
6 MBit/s
2000 t
Bit
3 MBit/s
1000 t
Bit
1.5 MBit/s
530 t
Bit
Table 4: Minimum slot time on OLM/G11-1300 and
OLM/G12-1300
Use the values from Table 4 if the calculated slot time is smaller than the minimum slot time indicated in the table.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...