4-1
PROFIBUS Optical Bus Terminal (OBT)
C79000-G8976-C122-02
Network Topology
4.1
Optical Bus
The OBT is operated in conjunction with other SIMATIC devices, for example the
IM 153-2 FO or IM 467 FO on the optical PROFIBUS DP in the form of an optical
bus.
Individual PROFIBUS DP nodes with an RS-485 interface are connected to
channel 1 of the OBT via a maximum 100 m long PROFIBUS cable with bus
connectors fitted at both ends. The terminating resistors on the bus connectors
must be activated. An active or passive PROFIBUS DP node can be connected.
The OBT can be included at any point in the optical bus. If it is included at the start
or end, the unused optical channel must be closed with the rubber plug supplied.
This prevents contamination of the optical elements and disturbances caused by
light entering the module.
The connection forming the optical bus is a two-fiber plastic FO cable (maximum
length 50 m) or PCF FO cable (maximum length 300 m). The fiber-optic cables
have two simplex connectors at each end.
The fiber-optic connection between two devices is established by connecting the
optical sender of one device with one fiber to the optical receiver of the other
device and the optical receiver of the one device to the optical sender of the other
device (cross-over connection).
If an OBT or a fiber-optic cable fails, the entire network becomes two subnets.
Depending on the location of the problem, individual devices may no longer be
accessible.
The OBT does not support the creation of single-fiber rings, of monitored optical
busses or redundant ring structures.
4
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...