Configuring Networks
3-30
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Note
The slot time calculation takes into account only the optical network and the
attachment of nodes to the OLM in each case via a maximum 20 m long RS-485
bus segment. Longer RS-485 bus segments must be included by adding them to
the length
FOC
.
With the OLM/G11-1300 and OLM/G12-1300, the minimum slot times shown in the
following table must be maintained at transmission rates of 12 Mbps, 6 Mbps, 3
Mbps and 1.5 Mbps.
Table 3-11 Minimum Slot Time for
OLM/G11-1300 and OLM/G12-1300
Transmission rate
Minimum slot
time
12 Mbps
3800 t
Bit
6 Mbps
2000 t
Bit
3 Mbps
1000 t
Bit
1.5 Mbps
530 t
Bit
When configuring the slot time, use the minimum slot time as shown in Table 3-11
if the calculated slot time is less than the minimum slot time.
Note
If the slot time is configured with a value that is too low, this can lead to
malfunctions and error displays on the OLM. The system LED flashes red/green.
3.3.3
Example of Configuring the Bus Parameters in STEP 7
Structure of the Network Example
The example assumes a redundant optical ring with the following structure:
S
20 OLM G12 modules in the redundant optical ring
S
20 km total ring length
S
Transmission Rate 1.5 Mbps
S
Nodes attached directly to OLMs
S
“PROFIBUS-DP” bus protocol
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...