General Instructions for Working with
SIMATIC NET PROFIBUS PCF Fiber Optic Cables
Please note the following instructions to avoid damage to cables:
F
Make sure that the selected cable is suitable for the area of application.
You should, for example, check the following:
– Required temperature range
– Resistance of the jacket materials to chemicals, water, oils, rodents etc.
to which the cable may be exposed in your application
– Required mechanical properties (bending radii, tensile strength, transverse compressive
strength)
– Required behavior of the cable in fire
– Suitability of the cable including the connectors for the devices to be interconnected
If necessary, use a special cable that meets your requirements. Your SIMATIC NET contact in your
local Siemens branch will be happy to advise you.
F
Never exceed the maximum permitted loads (tensile load, transverse compressive load etc.)
specified in the data sheet of the cable you are using. Excessive transverse compressive load can,
for example, result by using screw clamps to secure the cable.
F
Always use the pulling loop to pull in the PCF standard cable. Never pull in the cable by the
connectors or stripped cords.
F
Only use PCF fiber-optic cables with devices approved for this FO cable type. Keep to the maximum
permitted cable lengths.
F
When cutting cables to length, make sure that no loops are formed and that the cable is not twisted.
Loops and torsion under tensile load can cause kinks or cracks that may mean irreparable damage to
the cable.
F
Follow the steps outlined in these instructions.
F
Make sure that the outer jacket and buffers of the cable are not damaged.
F
Never insert contaminated connectors in the device sockets. The optical transmitter and receiver
elements could otherwise be destroyed.
F
When fitting the cable to connectors make sure that the transmitted and received data are crossed in
the cable.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...