Passive Components for RS-485 Networks
4-3
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 4-1
LAN Cables for PROFIBUS (1)
Technical Specifications
1)
Cable Type
FC Standard
Cable
FC FRNC
Cable
FC Food
Cable
FC Robust
Cable
FC Under-
ground Cable
Order Number
6XV1 830
-0EH10
6XV1 830
-0LH10
6XV1 830
-0GH10
6XV1 830
-0JH10
6XV1 830
-3FH10
Attenuation
at 16
MHz
at 4
MHz
at 38.4 kHz
at 9.6
kHz
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
< 42 dB/km
< 22 dB/km
< 4 dB/km
<2.5 dB/km
Characteristic impedance
at 9.6 kHz
at 31.25 kHz
at 38.4 kHz
at 3 to 20 MHz
Rated value
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
d.c. loop resistance
≤
110
Ω
/km
≤
110
Ω
/km
≤
110
Ω
/km
≤
110
Ω
/km
≤
110
Ω
/km
Shield resistance
≤
9.5
Ω
/km
≤
9.5
Ω
/km
≤
9.5
Ω
/km
≤
9.5
Ω
/km
≤
9.5
Ω
/km
Effective capacitance at
1 kHz
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28.5
nF/km
Operating voltage
(effective)
≤
100 V
≤
100 V
≤
100 V
≤
100 V
≤
100 V
Cable type
standard code
02YY(ST)CY
1x2x0.64/2.55-
150 KF 40
FRNC VI
02YSH(ST)CH
1x2x0.64/2.55-
150 VI KF25
FRNC
02YSY(ST)C2
Y
1x2x0.64/2.55-
150 KF40
02YSY(ST)C11
Y
1x2x0.64/2.5-
150 KF40
FRNC VI
02YSY(ST)
CY2Y
1x2x0.64/2.5-
150 KF 40 SW
Sheath
Material
Color
Diameter
PVC
violet
8.0
±
0.4 mm
FRNC
light violet
8.0
±
0.4 mm
PE
black
8.0
±
0.4 mm
PUR
violet
8.0
±
0.4 mm
PE/PVC
black
10.8
±
0.5 mm
3)
Permitted ambient conditions
– Operating temperature
– Transport/storage
temperature
– Installation temperature
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-25
°
C + 60
°
C
-25
°
C + 60
°
C
-25
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
Bending radii
One-time bending
Repeated bending
≥
75 mm
≥
150 mm
≥
75 mm
≥
150 mm
≥
75 mm
≥
150 mm
≥
75 mm
≥
150 mm
≥
80 mm
≥
150 mm
Max. tensile load
100 N
100 N
100 N
100 N
100 N
Weight approx.
76 kg/km
67 kg/km
67 kg/km
73 kg/km
117 kg/km
Halogen free
no
yes
no
no
no
Behavior in fire
flame-retardant
according to
VDE 0472
T804
test type C
flame-retardant
according to
VDE 0472
T804
test type C
flammable
flame-retardant
according to
VDE 0472
T804
test type B
flammable
Oil resistance
Conditionally
resistant to mi-
neral oil and
greases
Conditionally
resistant to mi-
neral oil and
greases
Conditionally
resistant to mi-
neral oil and
greases
good resi-
stance to mine-
ral oil and
greases
Conditionally
resistant to mi-
neral oil and
greases
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...