Topologies of SIMATIC NET PROFIBUS Networks
2-24
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Properties of the DP/PA Coupler (General)
The DP/PA coupler has the following characteristics:
S
Electrical isolation between PROFIBUS-DP and PROFIBUS-PA
S
Conversion of the physical transmission mechanism between RS-485 and IEC
61158-2
S
Diagnostics using LEDs
S
Transmission rate on PROFIBUS-DP 45.45 Kbps
S
Transmission rate on PROFIBUS-PA 31.25 Kbps
S
Integrated power supply unit
Properties of the DP/PA Coupler Ex [i]
The DP/PA coupler Ex [i] (6ES7 157-0AD00-0XA0) has the following additional
characteristics:
S
Type of Protection EEx [ia] II C
S
Intrinsic safety
S
Integrated, intrinsically safe power supply unit and integrated barrier
The DP/PA coupler Ex [i] (6ES7 157-0AD80-0XA0) has the following
characteristics that differ from the DP/PA coupler EX [i] (6ES7 157-0AD00-0XA0):
S
Type of protection EEx [ib] II C
S
Extended environmental conditions (SIMATIC outdoor)
Configuring the DP/PA Coupler
S
The DP/PA coupler can be used in SIMATIC S5 and S7 and with all DP masters
that support 45.45 Kbps.
S
The DP/PA coupler does not need to be configured. You must only set the
transmission rate of 45.45 Kbps for the relevant DP network during
configuration.
You then configure the PA field devices just as normal DP slaves using the DP
configuration tool and the appropriate GSD file. You can configure the PA field
devices with SIMATIC PDM or with any other vendor-specific software
configuration tool.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...