Passive Components for RS-485 Networks
4-5
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 4-2
LAN Cables for PROFIBUS (2)
Technical Specifications
1)
Cable Type
FC Trailing
Cable
6) 4)
Festoon
Cable
6) 4)
Flexible Cable
6) 4)
FC Process
Cable for IEC
61158-2
7)
SIENOPYR FR
Marine Cable
Order Number
6XV1 830
-3EH10
6XV1 830
-3GH10
6XV1 830
-0FH10
6XV1 830
-5EH10,
-5FH10
6XV1830
–0MH10
Attenuation
at 16
MHz
at 4
MHz
at 38.4 kHz
at 9.6
kHz
< 49 dB/km
< 25 dB/km
< 4 dB/km
< 3 dB/km
< 49 dB/km
< 25 dB/km
< 4 dB/km
< 3 dB/km
< 49 dB/km
< 25 dB/km
< 4 dB/km
< 3 dB/km
<= 3 dB/km
< 45 dB/km
< 22 dB/km
< 5 dB/km
< 3 dB/km
Characteristic impedance
at 9.6 kHz
at 31.25 kHz
at 38.4 kHz
at 3 to 20 MHz
Rated value
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
270
±
27
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
100
±
20
Ω
100
Ω
250
±
25
Ω
-
185
±
18.5
Ω
150
±
15
Ω
150
Ω
d.c. loop resistance
≤
133
Ω
/km
≤
133
Ω
/km
≤
133
Ω
/km
≤
44
Ω
/km
≤
110
Ω
/km
Shield resistance
≤
14
Ω
/km
≤
19
Ω
/km
≤
14
Ω
/km
-
-
Effective capacitance at
1 kHz
approx. 28.5
nF/km
approx. 28.5
nF/km
approx. 28 nF/
km
-
approx. 30 nF/
km
5)
Operating voltage
(effective)
≤
100 V
≤
100 V
≤
100 V
≤
100 V
≤
100 V
Cable type
standard code
02YY(ST)C11Y
1x2x0.64/2.55-
150 KF LI 40
FR petrol
02Y(ST)CY
1x2x0.65/2.56-
150 LI petrolFR
02Y(ST)C11Y
1x2x0.65/2.56-
150 LI VI
FRNC
02Y SY (ST)
CY
1x2x1.0/2.55-
100 BL OE FR
M-02Y(ST)CH
X
1x2x0.35
100V
Sheath
Material
Color
Diameter
PUR
petrol
8.0
±
0.4 mm
Special PVC
petrol
8.0
±
0.3 mm
PUR
violet
8.0
±
0.4 mm
PVC
blue / black
8.0
±
0.4 mm
Polymer
3)
black
10.3
±
0.5 mm
Permitted ambient conditions
– Operating temperature
– Transport/storage
temperature
– Installation temperature
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-40
°
C + 60
°
C
-20
°
C + 60
°
C
-20
°
C + 60
°
C
-20
°
C + 60
°
C
-40
°
C + 80
°
C
-40
°
C + 80
°
C
-10
°
C + 50
°
C
Bending radii
One-time bending
Repeated bending
≥
40 mm
≥
60 mm
2)
≥
30 mm
≥
70 mm
2
)
≥
60 mm
≥
120 mm
8)
≥
60 mm
≥
160 mm
≥
108 mm
≥
216 mm
Max. tensile load
100 N
80 N
100 N
150 N
100 N
Weight approx.
74 kg/km
56 kg/km
67 kg/km
103 kg/km
109 kg/km
Halogen free
no
no
yes
no
yes
Behavior in fire
flame-retardant
according to
VDE 0472
T804
test type B
flame-retardant
according to
VDE 0472
T804
test type B
flame-retardant
according to
VDE 0472
T804
test type B
flame-retardant
according to
VDE 0472
T804
test type B
flame-retardant
according to
VDE 0472
T804
test type C
Oil resistance
good resi-
stance to mine-
ral oil and
greases
conditionally
resistant to mi-
neral oil and
greases
good resi-
stance to mine-
ral oil and
greases
good resi-
stance to mine-
ral oil and
greases
very good resi-
stance to mine-
ral oil and
greases
UV resistance
yes
yes
yes
yes
yes
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...