6.1 Configuration of optical line and star topologies
29
6 Configuration
Version 1.0 8/00
6 Configuration
During configuration, the PROFIBUS network parameter "Slot time" must be adapted to the network coverage,
network topology and the data rate due to frame delays caused by lines and network components, as well as by
monitoring mechanisms in the network components.
6.1 Configuration of optical line and star topologies
The following configuration conditions must be fulfilled in the redundant optical ring
(for details see Chap. 3.3 ”Redundant optical ring“, p.13):
(1) Configuration of a non-existent bus subscriber
(2) Increasing the retry value to at least 3
(3) Checking and adjusting the slot time
Use the user-specific profile of the configuration tool to set the parameters under (2) and (3).
Calculate the slot time with the following equation:
Slot time = a + (b
.
Length
OF
) + (c
.
Number
OLM
)
”Slot time“
is the monitoring period in bit times
”Length
OF
“
is the sum of all the optical fiber lines (segment lengths) in the network.
The length must be given in km!
”Number
OLM
“
is the number of PROFIBUS OLMs in the network.
The factors a, b and c are dependent on the transmission rate and are listed in the tables below.
6.2 Configuration of redundant optical rings
The PROFIBUS network is configured, e.g. with SIMATIC STEP 7 (V5) or COM PROFIBUS (V5). The number of OLMs
(Number
OLM
) and overall line lengths can be entered in an input mask. The configuration tools control whether the
slot time in the selected communications profile can be retained. If this time is exceeded as a result of additional OLM
and optical fiber line runtimes, an error message is issued and the parameters are adapted accordingly.
Summary of Contents for SIMATIC NET PROFIBUS
Page 10: ...Contents viii PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 11: ...PROFIBUS NETWORKS 1 ...
Page 26: ...PROFIBUS NETWORKS 1 16 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 241: ...A 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Testing PROFIBUS A ...
Page 254: ...Testing PROFIBUS A 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 288: ...Installing LAN Cables C 26 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 325: ...F 1 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 Dimension Drawings F ...
Page 338: ...Dimension Drawings F 14 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 396: ...Infrared Link Modul ILM 6ZB530 3AC30 0BA1 54 Copyright by Siemens ...
Page 434: ......
Page 438: ...Contents ii PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 Contents ...
Page 450: ...Network Topology 4 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 458: ...Installation and Startup 5 8 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 460: ...Troubleshooting 6 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 464: ...Technical Specifications 7 4 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 468: ...References 9 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 470: ...Abbreviations 10 2 PROFIBUS Optical Bus Terminal OBT C79000 G8976 C122 02 ...
Page 478: ...References I 4 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...
Page 488: ...Glossary Glossary 8 PROFIBUS Networks SIMATIC NET 6GK1970 5CA20 0AA1 Release 2 05 2000 ...