You can find additional information on this in Function Manual
PCS 7 Process Control System;
Time Synchronization.
Recommendation
To increase the plant-wide time synchronism, separate the network for time synchronization of
the automation systems (referred to hereinafter as the TIME-Net) from the system bus.
Separation of the system bus
● Section of the system bus for synchronization of the AS with the central system clock
– This network only connects the time master (SICLOCK TC400) and the AS to each other.
– There is a direct connection between the central system clock and the first CPU (see
figure below).
● Section of the system bus for communication of the automation systems with other systems
(e.g. engineering system; OS)
– This network is connected via a separate communication channel (e.g. CP 443-1).
The figure shows an example of the connection of an H-system to the time master.
The two parts of the figure show the difference in the connection between the example
configurations:
6,&./2&.7&
6,&./2&.7&
7LPHVWDPSLQJVWDQGDUGFRQILJXUDWLRQ
7LPHVWDPSLQJZLWKDSUHFLVLRQRIPV
6\VWHPEXV
6\VWHPEXV
7LPHPDVWHU
[FRPPXQLFDWLRQVSURFHVVRURQV\VWHPEXVHJ&3
&HQWUDOV\VWHPFORFN
7LPHPDVWHU
7,0(1(7
7,0(1(7UHGXQGDQW
6,&/2&.7&
Figure 4-4
Application of configurations for time stamping
Plant planning
4.9 Time synchronization and time stamping
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD
53