EMC directive
2014/30/EU "Electromagnetic compatibility" (EMC directive)
Use in the industrial environment
SIMATIC products are designed for use in industry.
Area of applica‐
tion
Interference emission requirements
Interference immunity requirements
Industry
EN 61000-6-4
EN 61000-6-2
Use in residential areas
Note
The ET 200SP HA distributed I/O system is intended for use in industrial environments; when
used in residential areas, it can affect radio/television reception.
If you are using the ET 200SP HA distributed I/O system in residential areas, you must ensure
compliance to the regulations on the emission of radio interference according to EN 61000‑6‑3.
Suitable measures for achieving RF interference level Class B include, for example:
● Installation of the ET 200SP HA distributed I/O system in grounded control cabinets/boxes
● Use of filters in the supply lines
Use in the field of power plants
The ET 200SP HA distributed I/O system fulfills the EMC specifications according to
EN 61000‑6‑5.
9.1.3
Explosion protection
ATEX Approval
ATEX certification according to the following standards:
● EN 60079-15 (Electrical apparatus for potentially explosive atmospheres; Type of
protection "n")
● EN 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0:
General Requirements)
IECEx Approval
Approval to IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n") and IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General
requirements)
IECEx Ex nA IIC Tx Gc IEC Ex DEK 13.0011X
Technical specifications
9.1 Standards and approvals
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD