Climatic ambient conditions
The following table shows the permissible climatic ambient conditions for the ET 200SP HA
distributed I/O system.
Table 9-12
Climatic ambient conditions
Ambient conditions Permissible range
Comments
Temperature
● Horizontal installation: from
-40°C to 70°C
● Vertical installation: from -40°C
to 60°C
Note: No icing
Observe any load-dependent limitations.
Refer to the documentation of the employed component.
Tested according to IEC 60068-2-2 (Dry heat)
Air pressure
● From 1 080 hPa
(corresponds to a depth of
approximately -1 000 m)
● Up to 606 hPa
(corresponds to an elevation of
approximately 4 000 m)
The density of the air decreases with increasing altitude. The
cooling effect of air in accordance with the elevation is shown in
the following table on derating.
Relative humidity
From 10 to 95%
Max. 95% at +25 °C
Without condensation, corresponds to relative humidity (RH)
stress grade 2 in accordance with IEC 61131 part 2
Tested according to IEC 60068-2-78 (Damp heat)
Concentration of
pollutants
● SO
2
: <0.5 ppm
● RH: <60 %, no condensation
● H
2
S: <0.1 ppm
● RH: <60 %, no condensation
Test: 10 ppm; 4 days
Test: 1 ppm; 4 days
ISA-S71.04 severity level G1; G2;
G3
-
Derating
The cooling effect of air decreases at higher altitudes as a result of its lower density.
The table shows the derating factor for the maximum permissible ambient temperature
depending on the use of the devices at an elevation above sea level.
Table 9-13
Derating when devices are used at an elevation above sea level
Elevation above sea level
1)
Derating factor for ambient temperature
2)
(-1 000 m) up to 2 000 m
1.0
3 000 m
0.9
4 000 m
0.8
1)
Please note that I/O modules with relay contacts are only suitable for an elevation up to 3 000 m.
2)
Relating to the maximum permissible ambient temperature in °C for 2 000 m
Technical specifications
9.4 Mechanical and climatic environmental conditions
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD
145
Summary of Contents for SIMATIC ET 200SP HA
Page 6: ...Table of contents ET 200SP HA Distributed I O system 6 System Manual 08 2019 A5E39261167 AD ...
Page 181: ...Glossary ET 200SP HA Distributed I O system System Manual 08 2019 A5E39261167 AD 181 ...
Page 182: ...Glossary ET 200SP HA Distributed I O system 182 System Manual 08 2019 A5E39261167 AD ...