8.8
Resetting the interface module to factory settings
Function
The "Reset to factory settings" function resets the interface module to the factory state.
Procedure using STEP 7
Note
Redundant configuration
For an IO device with 2 interface modules (redundant configuration), this action must be
performed separately for each interface module.
To reset an interface module to factory settings using STEP 7, follow these steps:
Ensure that there is a direct connection to the interface module.
1. Select the IO device in HW Config.
2. Select the menu command Target system > Ethernet > Edit node.
The "Edit Ethernet Node" dialog window opens.
3. Click the "Browse" button and select the IO device in the selection window.
4. Click "OK".
5. Click the "Reset" button in the "Reset to factory settings" area.
6. Click "OK" in response to the security prompt.
Result: The interface module then performs "Reset to factory settings".
Result after resetting to factory settings
The following table shows the values of the interface module properties after a factory reset:
Table 8-4
Properties of the interface module as shipped
Properties
Value
Parameters
Default setting
IP address
Not available
Device name
Not available
MAC address
Available
I&M data
Identification data (I&M0) available
Maintenance data (I&M1, I&M2, I&M3) not available
Firmware version
Available
Maintenance
8.8 Resetting the interface module to factory settings
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD
129