Sinusoidal disturbance variables
The following tables show the electromagnetic compatibility of the ET 200SP HA distributed I/
O system to sinusoidal interference.
Table 9-3
HF radiation - sinusoidal interference
HF radiation according to IEC 61000-4-3/NAMUR NE21
Electromagnetic RF field, amplitude-modulated
Corresponds
to degree of
severity
80 MHz to 2.0 GHz
2.0 GHz to 6 GHz
3
10 V/m
3 V/m
80% AM (1 kHz)
Table 9-4
HF coupling - sinusoidal interference
RF coupling in accordance with IEC
61000-4-6
Corresponds to degree of severity
(10 kHz) 150 kHz to 80 MHz
3
10 V
rms
unmodulated
80% AM (1 kHz)
Table 9-5
Magnetic field IEC 61000-4-8
Magnetic field according to IEC
61000-4-8
Corresponds to degree of severity
50/60 Hz 100 A /m
5
50/60 Hz 1 kA/m for 1 s
5
Table 9-6
Voltage with power engineering frequency (line frequency)
Test according to IEC 61000-4-16
Corresponds to degree of severity
10 V
3
100 V for 1 s
3
Technical specifications
9.2 Electromagnetic compatibility