9.3
Shipping and storage conditions
Introduction
The ET 200SP HA distributed I/O system surpasses requirements for transport and storage
conditions according to IEC 61131‑2. The following information applies to modules that are
shipped and/or stored in their original packaging.
Table 9-9
Shipping and storage conditions for modules
Type of condition
Permissible range
Free fall (in shipping package)
≤1 m
Temperature
From -40 °C to +70 °C
Air pressure
1)
From 1080 hPa (corresponds to a depth of approx. -1000 m)
Up to 606 hPa (corresponds to an elevation of approx. 4000
m)
Relative humidity
5% to 95%, without condensation
Sinusoidal oscillations according to
IEC 60068-2-6
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
Impact according to IEC 60068-2-27
250 m/s
2
, 6 ms, 1000 shocks
1)
Note that I/O modules with relay contacts are only suitable for an elevation up to 3000 m (corresponds
to air pressure of around 690 hPa).
Technical specifications
9.3 Shipping and storage conditions
ET 200SP HA Distributed I/O system
142
System Manual, 08/2019, A5E39261167-AD
Summary of Contents for SIMATIC ET 200SP HA
Page 6: ...Table of contents ET 200SP HA Distributed I O system 6 System Manual 08 2019 A5E39261167 AD ...
Page 181: ...Glossary ET 200SP HA Distributed I O system System Manual 08 2019 A5E39261167 AD 181 ...
Page 182: ...Glossary ET 200SP HA Distributed I O system 182 System Manual 08 2019 A5E39261167 AD ...