Table 9-7
Asymmetrical conducted interference
Inspection according to IEC 61000-4-16
and IEC 61000-4-18
Corresponds to degree of severity
● 10 V - 1 V (15 Hz - 150 Hz)
● 1 V (150 Hz - 1.5 kHz)
● 1 V - 10 V (1.5 kHz - 15 kHz)
● 10 V (15kHz - 150 kHz)
3
See the table "Conditions for the design of field wiring".
Table 9-8
Damped oscillatory waves
Inspection according to IEC 61000-4-16
and IEC 61000-4-18
Corresponds to degree of severity
Signals:
● 1.0 kV (common mode, 1 MHz)
● 0.5 kV (differential mode, 1 MHz)
2
DC supply:
● 1.0 kV (common mode, 1 MHz)
● 0.5 kV (differential mode, 1 MHz)
● 0.5 kV (common mode, 10 MHz)
2
See the table "Conditions for the design of field wiring".
Conditions for the design of field wiring
To fulfill these requirements, the field wiring for the modules should be performed as stipulated
in the following table.
Module
Article number
Design of the field wiring
AI 16xI 2-wire HART HA
6DL1134-6TH00-0PH1
Shielded
AI16xTC/8xRTD 2-/3-/4-wire HA
6DL1134-6JH00-0PH1
Shielded
AI-DI16/DQ16x24VDC HART HA
6DL1133-6EW00-0PH1
Shielded
AQ 8xI HART HA
6DL1135-6TF00-0PH1
Shielded
DI 16x24VDC HA
6DL1131-6BH00-0PH1
Unshielded
DI 8x230VAC HA
6DL1131-6GF00-0PK0
Unshielded
DI 8x24..125VDC HA
6DL1131-6DF00-0PK0
Unshielded
DI 16xNAMUR HA
6DL1131-6TH00-0PH1
Shielded
DI 32x24VDC HA
6DL1131-6BL00-0PH1
Unshielded
DQ 16x24VDC/0,5A HA
6DL1132-6BH00-0PH1
Unshielded
DQ 32x24VDC/0.5A HA
6DL1132-6BL00-0PH1
Unshielded
AI16xTC/8xRTD 2-/3-/4-wire HA
6DL1134-6JH00-0EH1
Shielded
AI-DI16/DQ16x24VDC HART HA
6DL1133-6EW00-0EH1
Shielded
Technical specifications
9.2 Electromagnetic compatibility
ET 200SP HA Distributed I/O system
140
System Manual, 08/2019, A5E39261167-AD