27 / 176
Siemens
Web server OZW772... V6.0
CE1C5701en
Building Technologies
Commissioning
2015-10-12
·
Enter these settings if the Web Server sends e-mails (report faults / send
consumption file).
·
Additional information on e-mail settings is available in Section 8.2.
·
Automatically negotiate the securest connection:
TLS mode is selected automatically if the device sending the email and the
email provider support TLS.
Data point
Explanation, example
Address mail server
Default val: smtp.example.com
Setting val: max. 49 characters
Contact the Internet service provider for the
mail server's address (IP address) or name
(domain). Often referred to as the outgoing
mail server or SMTP server instead of mail
server.
—
Port number mail server
Default val: 25
Setting val: 1…65535
Port number 25 is default for the mail
server (and does not normally require
change).
—
E-mail address sender
Default val: [email protected]
Setting val: max. 49 characters
The setting corresponds to the e-mail
address of the Web Server.
The e-mail address is displayed in the
"From" field of each e-mail.
—
Authentication mail server
Default val: No
Setting val: No/Yes
Select
Yes
for mail server access with
authentication.
In this case, user name and password (see
next two data points below) are required.
—
User name
Default val: (blank)
Setting val: max. 49 characters
User name and password help authenticate
each e-mail via the mail server.
—
Password
Default val: (blank)
Setting val: max. 49 characters
Password and user name help authenticate
each e-mail via the mail server.
—
Signature line 1…10
Default val: (blank)
Setting val: max. 49 characters
Signature lines are transmitted with the e-
mail. It identifies the sender, e.g. the plant's
Internet address.
—
Path: Home > 0.2.150 OZW772.xx > Settings > Communication > USB
Data point
Explanation, example
UPnP localization
Default val: USB
Setting val: ---, Ethernet, USB
The Web Server registers its presence in the
network via the Universal Plug and Play
(UPnP) service.
—
Web Server registers its existence in the USB network, when
·
"UPnP localization = USB" is set
and
·
The connection between PC/laptop and the Web Server is active via USB.
Notes
USB
UPnP localization