155 / 176
Siemens
Web server OZW772... V6.0
CE1C5701en
Building Technologies
KNX S-Mode
2015-10-12
The device stats of changed devices is no longer up-to-date after transmitted
project data from ETS to the OZW.
OZW must be selected and updated with "Generate". Administrator or service user
rights are required.
Confirm with "OK".
OZW is now updated.
The changes can now be viewed in the menu tree.
The following changes are recognized and displayed on the device list as "Not
updated":
·
Writing and entire project
·
Write a project without changes
·
Add / delete /rename KNX pages.
·
Add /Delete /Change type/Rename data points.
Update transmitted
project data in OZW