159 / 176
Siemens
Web server OZW772... V6.0
CE1C5701en
Building Technologies
Appendix
2015-10-12
11 Appendix
11.1 General notes
Names of data points and message text, e.g. of faults, cannot contain special
characters or umlauts. Valid characters:
·
a…z and A…Z
·
0…9
·
! „ $ % & ‚ ( ) * + ` - . / : ; < = > ? "Space
When sent,
invalid characters
will be converted to "
?
" (question marks).
11.2 Diagnostics
11.2.1 Web Server fault codes
Fault code Web Server fault
Type of fault
General
0
No fault
No acknowledgement
1
Plant ok
No acknowledgement
2
Fault
No acknowledgement
3
No urgent fault
No acknowledgement
Communications
5000
No bus power supply
No acknowledgement
5001
System time failure (Web Server as slave)
No acknowledgement
5002
>1 clock time master
With acknowledgement
5003
Invalid time of day (Web Server time not or incorrectly entered) No acknowledgement
5012
Device failure (Bus) *
No acknowledgement
5023
Message receiver 1 not reached
No acknowledgement
5024
Message receiver 2 not reached
No acknowledgement
5025
Message receiver 3 not reached
No acknowledgement
5026
Message receiver 4 not reached
No acknowledgement
5027
Consumer receiver 1 not reached
No acknowledgement
5028
Consumer receiver 2 not reached
No acknowledgement
5029
Energy ind. receiver 1 not reached
No acknowledgement
5030
Energy ind. receiver 2 not reached
No acknowledgement
5034
Trend receiver 1 not reached
No acknowledgement
5035
Trend receiver 2 not reached
No acknowledgement
System configuration errors
6001
>1 identical device address (Devices have same address)
With acknowledgement
7001
Change local Admin'password
No acknowledgement
* Device failure (bus) is a fault generated by the Web Server for a failed device. As result, the device
failure (bus) is assigned to "System faults", whereas all other faults generated by the Web Server are
assigned as "Local faults".
Text entry
Note
Fault codes