42 / 176
Siemens
Web server OZW772... V6.0
CE1C5701en
Building Technologies
Commissioning
2015-10-12
2.9 Final
steps
2.9.1 Check
faults
The fault indicator displays the plant state.
No faults may be pending after commissioning. Additional information on faults is
available in Section 4.3.
The fault indicator remains green as long as no fault is pending.
The fault indicator changes to red for faults. The most severe plant faults are
displayed.
·
Device name
·
Fault text
2.9.2 Final steps on Web Server
The final function checks are conducted on the Web Server, the cover is mounted
and the LEDs checked.
On display and operating elements, see Section 1.2.
Procedure:
1. Unplug USB cable.
2. Switch off message inhibition and address mode.
– Switch 8 must be set to "Off"
– Address mode LED
must be off.
3. Mount terminal cover.
4. Press
Remote
button for more than 6 seconds.
– The Web Server sends a system report to the defined message receivers.
– Fault LED displays (flashing) error in establishing communications.
5. LED
On
must be steady green.
6. Fault
LED
must be off.
Fault indication
Notes
No fault
Fault
Final steps
Note