COMBIMASTER & MICROMASTER Integrated
REFERENCE MANUAL
©
Siemens plc. 1999
| G85139-H1731-U300-D2
36
Parameter
Function
Range
[Default]
Description / Notes
P723
State of digital inputs
0 - 7
[-]
DIN3
DIN2
DIN1
0
=
0
0
0
1
=
0
0
1
2
=
0
1
0
3
=
0
1
1
4
=
1
0
0
5
=
1
0
1
6
=
1
1
0
7
=
1
1
1
P845
Motor current limit for
Flying Start (%)
0 - 250
[50]
(SW
Version :
3.00
onwards)
The motor current can be limited with this parameter. If
the set value is exceeded during flying start, the output
frequency is reduced until the current falls below this limit.
During this process, both LEDs will flash
(see Operating
Information section)
. If trip occurs during flying start, this
value should be reduced.
P880
Specific to PROFIBUS-DP. See PROFIBUS Handbook for
further details. (Access only possible with P099 = 1.)
P910
••••
Local/Remote mode
0 - 4
[0]
Sets the inverter for local control or remote control over the
serial link:
0
= Local control
1
= Remote control (and setting of parameter values)
2
= Local control (but remote control of frequency)
3
= Remote control (but local control of frequency)
4
= Local control (but remote read and write access to
parameters and facility to reset trips)
When operating the inverter via remote control (P910 = 1 or
3), the analogue input remains active when P006 = 1 and is
added to the setpoint.
P918
••••
Drive Address
0 - 255
[0]
Specific to PROFIBUS-DP/CAN. See PROFIBUS / CAN
Handbooks for further details. (Access only possible
with P099 = 1 or 2).
Each communications object is defined as a combination of
base address and offset whereby the offset is referred to the
value in P918.
P922
Software version
0.00 –
99.99
[-]
Contains the software version number and cannot be
changed.
P923
••••
Equipment system
number
0 – 255
[0]
You can use this parameter to allocate a unique reference
number to the inverter. It has no operational effect.
P927
••••
Local or Remote
Access for Parameters
0 – 1
[0]
Specific to PROFIBUS-DP/CAN. See PROFIBUS / CAN
Handbooks for further details. (Access only possible
with P099 = 1 or 2).
Determines which parameter access interface can write to
parameters. Note that read access is always allowed.
0
= Parameter write access via keypad.
1
= Parameter write access via Comms module.