COMBIMASTER & MICROMASTER Integrated
REFERENCE MANUAL
©
Siemens plc. 1999
| G85139-H1731-U300-D2
26
Parameter
Function
Range
[Default]
Description / Notes
P031
••••
Jog frequency right
(Hz)
0 - fmax**
[5.00]
Jogging is used to advance the motor by small amounts. It is
controlled via the JOG button or with a non-latching switch
on one of the digital inputs (P051 to P053).
If jog right is enabled (DINn=7), this parameter controls the
frequency at which the inverter will run when the switch is
closed. Unlike other setpoints , it can be set lower than the
minimum frequency.
P032
••••
Jog frequency left
(Hz)
0 - fmax**
[5.00]
If jog left is enabled (DINn=8), this parameter controls the
frequency at which the inverter will run when the switch is
closed. Unlike other setpoints , it can be set lower than the
minimum frequency.
P033
Jog ramp up time
(seconds)
(SW Version : 3.00
onwards)
0.00 –
650.00
[10]
This is the time taken to accelerate from 0Hz to maximum
frequency (P013) for jog functions. It is
not
the time taken to
accelerate from 0Hz to the jog frequency. If DINn =16
(see
P051 to P053)
then this parameter can be used to override th
normal Ramp-up time set by P002.
P034
Jog ramp down time
(seconds)
(SW Version : 3.00
onwards)
0.00 –
650.00
[10]
This is the time taken to decelerate from maximum frequency
0Hz to (P013) for jog functions. It is
not
the time taken to
decelerate from the jog frequency to 0Hz. If DINn =16
(see
P051 to P053)
then this parameter can be used to override th
normal Ramp-down time set by P003.
P035
Reverse motor
direction
0 – 1
[0]
0
= Normal direction control.
1
= Direction control is reversed.
P041
••••
Fixed frequency 1
(Hz)
0 - fmax**
[5.00]
Valid if P006 = 2 and P053 = 6 or 18
or P051 = P052 = P053 = 17.
P042
••••
Fixed frequency 2
(Hz)
0 - fmax**
[10.00]
Valid if P006 = 2 and P052 = 6 or 18
or P051 = P052 = P053 = 17.
P043
••••
Fixed frequency 3
(Hz)
0 - fmax**
[15.00]
Valid if P006 = 2 and P051 = 6 or 18
or P051 = P052 = P053 = 17.
P044
••••
Fixed frequency 4
(Hz)
0 - fmax**
[20.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P045
Inversion fixed
setpoints for
fixed frequencies
1 - 4
0 - 7
[0]
Sets the direction of rotation for the fixed frequency.
FF1
FF2
FF3
FF4
P045 = 0
⇒
⇒
⇒
⇒
P045 = 1
⇐
⇒
⇒
⇒
P045 = 2
⇒
⇐
⇒
⇒
P045 = 3
⇒
⇒
⇐
⇒
P045 = 4
⇒
⇒
⇒
⇐
P045 = 5
⇐
⇐
⇒
⇒
P045 = 6
⇐
⇐
⇐
⇒
P045 = 7
⇐
⇐
⇐
⇐
⇒
Fixed setpoints not inverted.
⇐
Fixed setpoints inverted.
P046
••••
Fixed frequency 5
(Hz)
0 - fmax**
[25.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P047
••••
Fixed frequency 6
(Hz)
0 - fmax**
[30.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.