COMBIMASTER & MICROMASTER Integrated
REFERENCE MANUAL
©
Siemens plc. 1999
| G85139-H1731-U300-D2
28
Parameter
Function
Range
[Default]
Description / Notes
Value
Function of
P051 to P053
Function
low state
Function
high state
0
Input disabled
-
-
1
ON right
Off
On Right
P051
Selection control
function, DIN 1
(terminal 5), fixed
frequency 3 or binary
fixed frequency bit 0
0-19
[1]
2
On Left
Off
On Left
3
Reverse
Normal
Reverse
4
OFF 2
OFF 2
On
5
OFF 3
Off 3
On
6
Fixed Frequencies
1 – 3
Off
On
7
Jog Right
Off
Jog right
P052
Selection control
function, DIN 2
(terminal 6), fixed
frequency 2 or binary
fixed frequency bit 1
0-19
[2]
8
Jog left
Off
Jog left
9
Remote operation
Local
Remote
10
Fault code reset
Off
Reset on
rising edge
11
Increase frequency *
Off
Increase
12
Decrease frequency*
Off
Decrease
13
Disable analogue input
(setpoint is 0.0 Hz)
Analogue
on
Analogue
disabled
14
Disable the ability to
change parameters
‘P’ Enabled
‘P’ disabled
15
Enable dc brake
Off
Brake on
16
Use jog ramp times
instead of normal ramp
times
(SW Version : 3.00
onwards)
Normal
Jog Ramp
Times
17
Binary fixed frequency
control (fixed
frequencies1-7)
Off
On
P053
Selection control
function, DIN 3
(terminal 7), fixed
frequency 1 or binary
fixed frequency bit 2
0-19
[10]
18
As 6, but input high will
also request RUN
Off
On
19
External trip / PTC
Trip (F012)
No Trip
* Only effective when P007 = 0.
Binary Coded Fixed Frequency Mapping
(P051, P052, P053 = 17)
DIN3
(P053)
DIN2
(P052)
DIN1
(P051)
STOP
0
0
0
Run to FF1 (P041)
0
0
1
Run to FF2 (P042)
0
1
0
Run to FF3 (P043)
0
1
1
Run to FF4 (P044)
1
0
0
Run to FF5 (P046)
1
0
1
Run to FF6 (P047)
1
1
0
Run to FF7 (P048)
1
1
1