4.5 Control Cable Connections
CAUTION
The control and power supply cables must be laid separately. They must not be fed through
the same cable conduit / trunking.
Use screened cable for the control lead.
Feed the control cable into the inverter via
the appropriate gland hole
.
Connect the
control wires in accordance with the
information in Figures 4, 5 and 6, having first
unplugged connector block PL800 from the
PCB (CS B only).
IMPORTANT:
A wire link
must
be fitted
between control terminals 5 (DIN1) and 1
(P10+) if it is required to start the inverter
from the control potentiometer R314, or the
analogue input.. The wire link must be
removed when operation via a run/stop
switch is required.
COMBIMASTER Control Terminal
Cabling Information
CS A (PL700):
CS B (PL800)
Cable AWG
22 – 18
28 – 20
= approx. mm2
0.35 – 0.82
0.08 – 0.50
Strip Length (mm)
5 – 6
5 – 6
Strip Length (inch)
0.22
0.22
Note that the optional
potentiometer fitted as an
analogue set point shown in
Figure 4 & 5 assumes that
jumper JP304 is connecting 0V
(pin 2) to AIN- (pin 4).
+15V can be used as an
alternative to P10+ for the
digital inputs.
Plug the connector block back into the PCB
(CS B only), refit the cover and tighten the
four securing screws.
12
11
10
9
8
7
6
5
5
4
4
3
3
2
2
1
1
PI+
PI-
+15V
JP305
JP304
1 - +5V (250mA max.)
2 - N (-)
3 - 0V
4 - P (+)
5 - no connection
PI Power Supply
(+15V,
max. 50mA)
PI +ve Input
(0 - 10V
or 0 - 20mA)
RLB
(NO)
RLC
(COM)
Relay (RL1)
(30V dc. 1.0 A max.)
Digital Inputs
(7.5 - 33V, max. 5mA)
PL800 (CS B) / PL700 (CS A)
SK200 Socket
DIN3
DIN2
DIN1
AIN-
AIN+
0V
P10+
Analogue Input
(0/2 - 10V,
or 0/4 - 20mA)
Power Supply
for Digital and
Analogue
Inputs
(+10V, max. 10mA)
PI -ve Input
Figure 4 Control Terminal Connections