COMBIMASTER & MICROMASTER Integrated
REFERENCE MANUAL
©
Siemens plc. 1999
| G85139-H1731-U300-D2
47
Installation should be in conformance with
EMC directives and regulations (
this is
described in section 4 and in the operating
manuals for the PLC
).
Dimensions
H x W x D
115 mm x 90 mm x
30 mm
Degree of protection
IP 65
Maximum bus
speed
12MBd
Table 6: Technical Data
7.3 Control and Commissioning with
SIMOVIS
The SIMOVIS drive commissioning software
operates under Windows 95 or NT and can be
used to configure the COMBIMASTER,
MICROMASTER, MICROMASTER Vector and
MIDIMASTER Vector drives.
SIMOVIS offers the following benefits:
•
Access from the same PC to one or
several drives connected to the same
serial bus.
•
Storage of parameter sets on the PC.
•
Control and monitoring of the drives.
•
Simplified, text driven, access to all
parameters within the drive.
•
Upread and download of entire
parameter sets.
•
Off-line configuration for altering
parameter sets stored on the PC hard
disk drive without a connection to the
drive.
•
Interface to the S7 Manager to allow
configuring of drives on a PROFIBUS
DP* link within an automation system.
* Requires a communication board to
operate via PROFIBUS
–Ref No.
6GK1541-1AA00 PROFIBUS CP5411.
The minimum recommended PC
specification for operation of
SIMOVIS is a 90MHz Pentium
with 32MB of RAM, 200MB hard
drive and WINDOWS95 or NT4.0
Designation
Order No.
SIMOVIS Standalone
Version
6SE3290-0XX87-8SA2
Block package for
SIMATIC S7 including
DVA_S7 and Object
Manager
6SX7005-0CB00
Table 7: SIMOVIS Ordering Information
Standalone Operation of SIMOVIS
For direct configuration of one or more drives,
SIMOVIS communicates over the PC serial
port, COM1 or COM2. An RS232/485
converter must be connected between the PC
and the drive. The Clear Text Display module
is suitable for this purpose – refer to section
7.1.
Following installation, the Buskon program
must be called to define whether one or more
drives is connected to the PC. For each
connected drive, the drive type must be
selected from the hardware directory and the
bus address must match the value
programmed into P091 in the drive.