5-7
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
5.2.2
Structure of the Slave Diagnosis
The diagnostics of the ET 200L/ET 200L-SC/ET 200L-SC IM-SC distributed
I/O device comply with EN 50710 Volume 2, PROFIBUS. The slave diagno-
sis is explained below.
The slave diagnosis comprises 6 bytes for the ET 200L and not more than
17 bytes for the ET 200L-SC/ET 200L-SC IM-SC:
Byte 0
Byte 1
Byte 2
Byte 5
Byte 3
Byte 4
Station statuses 1 to 3
Master PROFIBUS address
High byte
Low byte
Manufacturer ID
Byte 6
Byte 7
Byte 8
Module diagnosis
for the ET 200L-SC or
ET 200L-SC IM-SC
Byte 9
Byte 16
Station diagnosis
for ET 200L-SC or
ET 200L-SC IM-SC
.
.
ET 200L
ET 200L-SC
Figure 5-1
Structure of the Slave Diagnosis
You can request a slave diagnosis with the following function blocks:
Table 5-3
Function Blocks for Slave Diagnosis
PLC Family
Number
Name
SIMATIC S5 with IM 308-C
FB 192 192
FB IM308C
SIMATIC S7/M7
SFC 13 13
SFC “DPNRM_DG”
S5-95U with DP master interface
FB 230 230
FB S_DIAG
SIMATIC S5 with
CP 5431 DP/FMS
Communication function blocks (see
standard FBs) SEND and RECEIVE
with job number 209
Introduction
Structure of the
Slave Diagnosis
Requesting a
Slave Diagnosis
Diagnostics