10-20
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Table 10-1
Switching capacity and lifetime of the contacts
With Resistive Load
Voltage
Current
Number of Operations
(Typ.)
DC 24 V
5.0 A
0.1 million
DC 24 V
1.0 A
0.5 million
DC 24 V
0.5 A
1.5 million
DC 60 V
0.5 A
1.0 million
DC 120 V
0.2 A
1.0 million
AC 48 V
5.0 A
0.3 million
AC 60 V
5.0 A
0.2 million
AC 120 V
5.0 A
0.1 million
AC 120 V
1.0 A
1.0 million
AC 120 V
0.5 A
2.5 million
AC 230 V
5.0 A
0.2 million
AC 230 V
1.0 A
0.5 million
AC 230 V
0.5 A
1.5 million
For Inductive Load in Accordance with IEC 947-5-1 DC13/AC15 and Lamp
Load
Voltage
Current
Number of Operations
(Typ.)
DC 24 V
1.0 A
0.1 million
DC 24 V
0.5 A
0.5 million
DC 60 V
0.5 A
0.5 million
DC 120 V
0.2 A
0.1 million
AC 48 V
2.0 A
1.0 million
AC 60 V
2.0 A
1.0 million
AC 120 V
2.0 A
0.5 million
AC 120 V
1.0 A
0.7 million
AC 120 V
0.7 A
1.0 million
AC 120 V
0.5 A
2.0 million
AC 230 V
2.0 A
0.2 million
AC 230 V
1.0 A
0.5 million
AC 230 V
0.5 A
1.0 million
The lifetime is longer with an external suppression circuit.
SC Digital Electronic Modules – Technical Data