C-28
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Table C-13
ET 200L-SC IM-SC Example, continued
Byte
Meaning
Value
24
01
H
Channel module address: slot A
Data record 128
(digital)
25
01
H
Channel module-specific identifier: 01
H
S
C
(digital)
26
00
H
Byte offset, input range: 0
Smart Connect
2DIDC24V on
27
0A
H
Bit offset: 2; number of channels: 1 (two-chan-
nel); input range
2DIDC24V on
slot A
28
FF
H
Byte offset, output range: no output
29
FF
H
Bit offset: 0; number of channels: 0; output
range
30
00
H
Channel module-specific parameters
31
02
H
Channel module address: slot B
32
02
H
Channel module-specific identifier: 02
H
S
C
33
FF
H
Byte offset, input range: no input
Smart Connect
2DODC24V0.5A
34
FF
H
Bit offset: 0; number of channels: 0 ; input
range
2DODC24V0.5A
on slot B
35
00
H
Byte offset, output range: 0
36
0C
H
Bit offset: 4; number of channels 1 (two- chan-
nel); output range
37
00
H
Channel module-specific parameters
38
07
H
Block length
Data record 0
(analog)
39
5F
H
S7 constant
(analog)
40
05
H
Slot
41
00
H
Data record number
42
02
H
Data record length
43
00
H
Diagnostics enable: 0 (as DS0 digital)
44
00
H
Not applicable
45
1C
H
Block length
Data record 128
(analog)
46
17
H
S7 constant
(analog)
47
05
H
Slot
48
80
H
Data record number
49
17
H
Data record length
50
00
H
Version identifier
51
50
H
Additional identifier/device type assignment
52
03
H
Channel module address: slot C
Smart Connect
2AI U +/ 10 V
53
C5
H
Channel module-specific identifier: C5
H
2AI U +/– 10 V
in slot C
54
00
H
Byte offset input range 0
in slot C
55
88
H
Bit offset: 0; channel number: 1 (two-channel);
channel length: 2 bytes
56
FF
H
Byte offset output range: no output
57
FF
H
Bit offset: 0; channel number: 0; output range
58
00
H
Channel module-specific parameters
Configuration Frame and Parameterization Frame for the ET 200L