8-14
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Galvanic isolation
Between channels
No
Between channels and
PROFIBUS-DP
Yes
Insulation tested with
500 V DC
Power input
from supply voltage
L4+/L5+
Max. 70 mA
from load voltage L1+
and L2+/L3+ (without
load)
Max. 100 mA per load
group
Power loss of module
Typically 7 W
Status, Interrupts, Diagnostics
Status display
Green LED per channel
Interrupts
None
Diagnostic function
Yes
Bus monitoring
PROFIBUS-DP
Red ”BF” LED
Monitoring of electro-
nics power supply
Green ”ON” LED
Actuator Selection Data
Output voltage
At signal ”1”
At least L1+ (– 3 V) or
L2+/L3+ (3 V)
Output current
At signal ”1”
Rated value
Permissible range
0.5 A
1 mA to 0.5 A
At signal ”0”
(residual current)
Max. 1 mA
Output delay (with resistive load)
With ”0” after ”1”
Max. 50
µ
s
With ”1” after ”0”
Max. 200
µ
s
Load resistance range
41
W
to 28 k
W
Lamp load
Max. 5 W
Parallel connection of two outputs
For redundant control
of load
Possible (outputs in same
group only)
For performance im-
provement
Not possible
Driving a digital input
Possible
Switching frequency
Resistive load
Max. 100 Hz
Inductive load to
IEC 947-5-1, DC13
Max. 0.5 Hz
Lamp load
Max. 8 Hz
Limitation of voltage in-
duced on circuit interrup-
tion
Typically L1+ (– 55 V) or
L2+/L3+ (55 V)
Short-circuit protection
Response threshold
Yes
Typically 0.7 A
ET 200L Electronics Blocks – Technical Data