Figure C-6 describes the contents of data record 128. These bytes are re-
peated for each Smart Connect electronic module that is connected.
Channel module-specific identifier of
the Smart Connect electronic module
Channel module address of the Smart
Connect electronic module
Byte offset, input range of the SC
section (see Table C-5)
Byte 7, 14 to 56
Byte 8, 15 to 57
Byte 9, 16 to 58
01
H
to 08
H
00
H
to 1F
H
or 3F
H
/
FF
H
No input
Byte offset 31 (ET 200L-SC) or 63 (ET 200L-SC IM-SC)
Byte offset 0
Byte 10, 17 to 59
0
1
7
6 5
4 3
2
Bit offsets 0 to 7: Determine the position within
the byte in the input range (not applicable if the
byte offset is FF
H
)
Number of channels of the Smart Connect electronic module:
0 - single-channel; 1 - two-channel; 2 - three-channel
Byte 11, 18 to 60
Byte 12, 19 to 61
Byte 13, 20 to 62
00
H
0 0
Length requirements of channels
00 - 1 bit; 10 - 2 bytes
Byte offset, input range of the SC
section (see Table C-5)
No input
Byte offset 31 (ET 200L-SC) bzw. 63 (ET 200L-SC IM-SC)
Byte offset 0
0
1
7
6 5 4 3
2
Bit offsets 0 to 7: Determine the position within
the bytes in the input range (not applicable if the
byte offset is FF
H
)
Number of channels of the Smart Connect electronic module:
0 - single-channel; 1 - two-channel; 2 - three-channel
0 0
Length requirements of channels
00 - 1 bit; 10 - 2 bytes
Channel-module specific parameters
01
H
: 2DIDC24V or 1DIAC120/230V
02
H
: 2DODC24V0.5A; 2DODC24V2A; 1DOAC120/230V1A or
1DORel.AC230V
C5
H
: AI RTD; 2AI U; 2AI I or 2AI TC
D5
H
: Fast 2AI U or 2AI I
E6
H
: 1AO U or 1AO I (double module width)
D9
H
: 1COUNT40kHz
00
H
to 1F
H
or 3F
H
/
FF
H
Figure C-6
Structure of Data Record 128, Bytes 7 to 62
Data Record 128,
Contents
Configuration Frame and Parameterization Frame for the ET 200L