12-52
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The 1 AO U electronic module uses the following parameters:
Table 12-10
Static Parameters of the 1 AO U Electronic Module
Parameter
Value Range
Default Parameters
Measurement type
Deactivated
Voltage
Voltage
Output range (voltage)
"
10 V
1 ... 5 V
"
10 V
Interference frequency suppression
50 Hz (integration time 60 ms)
60 Hz (integration time 50 ms)
50 Hz
Smoothing
None
Weak
Medium
Strong
None
Format
SIMATIC S7
SIMATIC S5
SIMATIC S7
If you have not set the parameters of the 1 AO U electronic module using the
specified software (see Chapter 4), the default settings apply to both input
channels after a restart (see Table 12-10).
Parameters
Default Parameters
SC Analog Electronic Modules – T
echnical Data