C-18
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The data records for the ET 200L-SC IM-SC are arranged in the following
order:
Table C-10
Data Records for the ET 200L-SC IM-SC
Parameter
Record
Slot
Length
Meaning
Record
Digital SC
Modules
Only
Analog SC
Modules
Only
Digital and
Analog SC
Modules
g
g
DS0
SC digital
4
4
7 bytes
Diagnostic interrupt for the
digital Smart Connect
modules
DS128
SC digital
4
4
7 bytes
+ 7 bytes per SC module
Configuration data for the
digital Smart Connect
modules
DS0
SC analog
4
5
7 bytes
Diagnostic interrupt for the
analog Smart Connect
modules
DS128
SC analog
4
5
7 bytes
+ 7 bytes per SC module
Configuration data for the
analog Smart Connect
modules
DS130
SC analog
4
5
7 bytes
+ 2 bytes per analog SC
module
+ 5 bytes per channel
+ 11 bytes per counter
module
Parameters for the analog
Smart Connect modules
Parameters for the counter
module
Note
You must always transfer the complete parameterization frame for the con-
figuration of the ET 200L-SC or ET 200L-SC IM-SC.
The information in records DS128 and DS130 for the analog Smart Connect
modules must correspond.
Configuration
ET 200L-SC IM-SC
Configuration Frame and Parameterization Frame for the ET 200L