11-32
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
11.21 Analog Value Representation for Analog Input Modules in S7 Num-
ber Format
The tables in this section contain the measurement representations for the
individual measurement ranges of the analog input modules. The table values
apply to all modules with the corresponding measurement ranges.
The following tables contain the digitized analog values for the various mea-
surement ranges.
Since the binary representation of the analog values is always the same, the
following tables contain only the measurement ranges against the units.
For the corresponding binary representation of the measured values, see the
tables in Section 11.20.
Measured
Value in %
System
Voltage Measurement Range
Dec.
Hex.
±
10 V
±
80 mV
u
117.589 %
32767
7FFF
u
11.759V
Overflow
117.589 %
32511
7EFF
11.759 V
94.1 mV
Overrange
27649
6C01
g
100.000 %
27648
6C00
10 V
80 mV
Rated range
0.003617 %
1
1
361.7
V
2.89
V
0 %
0
0
0 V
0 V
– 0.003617 %
– 1
FFFF
–361.7
V
– 2.89
V
– 100.000 %
– 27648
9400
– 10 V
– 80 mV
– 27649
93FF
Underrange
– 117.593 %
– 32512
8100
-11.759 V
-94.1 mV
g
t
117.593 %
–32768
8000
t
-11.759V
t
-94.1mV
Underflow
How to Read the
Measurement
Tables
Voltage
Measurement
Range +10 V and
+80 mV