C-24
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
The contents of the data record for the 1COUNT40kHz counter module are
shown in the following figure:
Byte 10
Channel module address
Channel address
Total block length for a module
Block length for a channel
Byte 7
Byte 8
Byte 9
Byte 11
01
H
to 08
H
00
H
0B
H
Byte 12
Byte 13
09
H
Byte 15
Byte 14
Byte 16
Byte 17
Channel-specific parameters
Figure C-10 Structure of Data Record 130 for the 1COUNT40kHz Counter Module
The purpose of bytes 11 and 16 of data record 130 for analog input modules
is indicated in Table C-11.
Table C-11
AI Parameters in Byte 11 and 16 of DS130
Smart Connect
Module
Measurement Type
Measurement Range
Bit
1
Module
yp
g
7 ... 4
3 ... 0
–
Deactivated
0000
0000
2AI U
Voltage measurement
1 ... 5 V
0001
0111
g
+/– 10 V
1001
2AI I
Current measurement, 4-wire connection
0 ... 20 mA
0010
0010
4 ... 20 mA
0011
+/– 20 mA
0100
Current measurement, 2-wire connection
4 ... 20 mA
0011
0011
1AI RTD
Resistance measurement, 4-wire connection
0 ... 600
Ω
0100
0110
Thermal resistance measurement with lineariza-
tion and 4 wire connection
Pt100 Kl (climatic range)
1000
0000
tion and 4-wire connection
Pt100
0010
NI100
1011
2AI TC
Voltage measurement
+/– 80 mV
0001
0001
Temperature measurement with thermocouple
Type R
1011
0011
p
p
Type J
0101
Type K
1000
1
No other values or combinations are permissible
Data Record 130,
1COUNT40kHz
AI Module –
Byte 11 or Byte 16
Configuration Frame and Parameterization Frame for the ET 200L