C-35
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
For the default setting of the ET 200L-SC IM-SC, 4 bytes each are set in the
process image for the digital Smart Connect modules for the input and output
of the Smart Connect electronics modules.
SC modules
Input bytes
Output bytes
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
Byte 0
Byte 1
Byte 2
Byte 3
Slots
TB 16IM-SC
TB 16SC
Figure C-15 Default Setting for Digital SC Modules with the ET 200L-SC IM-SC
A default start-up is carried out with the following configuration:
ET 200L-SC 16 DO DC 24 V/0.5A and Smart Connect:
Smart Connect
Output word 64
Input word 70
Output word 80
ET 200L-SC
16 DO DC 24 V/0,5A
A
B
C
D
E
F
G
H
2DI
2DI 2DO 2DO 1DI 1DI
1DO
Rel
1DO
Rel
Address assignment for the ET 200L-SC and Smart Connect
ET 200L-SC 16 DO DC 24 V/0.5 A
–
On-board I/O device outputs 1 to 8: output byte 64.0 to 64.7
–
On-board I/O device outputs 9 to 16: output byte 65.0 to 65.7
Smart Connect:
Slot
SC Module
Address
A
2DIDC24V
Input
70.0 and 70.1
B
2DIDC24V
Input
70.2 and 70.3
C
2DODC24V0.5A
Output
80.4 and 80.5
D
2DODC24V0.5A
Output
80.6 and 80.7
E
1DIAC120/230V
Input
71.0
F
1DIAC120/230V
Input
71.2
G
1DORel.AC230V
Output 81.4
H
1DORel.AC230V
Output 81.6
Default Setting for
the ET 200L-SC
IM-SC
Example
Solution of the
Example
Configuration Frame and Parameterization Frame for the ET 200L