8-33
ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device
EWA 4NEB 780 6009-02c
Voltages, Currents, Potentials
Supply voltage L1
S
Rated voltage
120 VAC
S
Permissible range
74 to 132 VAC
S
Frequency
47 to 63 Hz
S
Power failure
withstand time
At least 20 ms
Aggregate current of outputs (per point)
S
Horizontal installation
up to 40
_
C
Max. 2 A
up to 60
_
C
Max. 1 A
S
All other installation
positions
up to 40
_
C
Max. 1A
Optical isolation
S
Between channels
Yes
S
Between L1 and
PROFIBUSDB
Yes
S
Between channels and
PROFIBUS-DP
Yes
Insulation tested with
1500 VAC
Power input
S
from supply voltage L
Max. 160 mA
Power loss of module
Typically 15.1 W
Status, Alarms, Diagnostics
Status display
Green LED per channel
Alarms
None
Diagnostic function
Yes
S
Bus monitoring
PROFIBUS-DP
Red ‘‘BF” LED
S
Monitoring of
electronics
power supply
Green ‘‘ON” LED
Sensor Selection Data
Input voltage
S
Rated value
120 VAC
S
With signal 1
74 to 132 VAC
S
With signal 0
0 to 20 VAC
Input current
S
With signal 1
9 to 27 mA
S
With signal 0
0 to 4 mA
Input delay
S
From 0 to 1
2 to 14 ms
S
From 1 to 7
6 to 25 ms
Input characteristic
To IEC 1131-2 Type 2
Connection of 2-wire
BEROs
Possible
Actuator Selection Data
Load voltage L
S
Rated voltage
24 V DC or 120 VAC
S
Permissible DC range
4.5 to 30 V DC
S
Permissible AC range
6 to 132 VAC
S
AC Frequency
47 to 63 Hz
Output voltage
S
With signal 1
At least L (– 1.0V)
Output current
S
With signal 1
Rated value
Permissible range
2.0 A Pilot Duty
10 mA to 2.0 A
S
With signal 0
(residual current)
none
Output delay (with
resistive load)
Max. 10 ms
Size of motor starter
S
Up to 40
_
C
NEMA Size 5
S
Up to 60
_
C
NEMA Size 4
Lamp load
Max. 50 W
Parallel connection of two outputs
S
For redundant control
of load
Possible
S
For performance
improvement
Not possible
Driving a digital input
Possible
Switching frequency
S
Resistive load
Max. 10 Hz
S
Inductive load
Max. 0.5 Hz
S
Lamp load
Max. 1 Hz
Short-circuit protection
No
ET 200L Electronics Blocks – Technical Data