Appendices
Appendix E – Modbus VERIS H8035/H8036 Emulation
98
Building Technologies
125-202
06/06/2017
For example, if the MD-BMS or MD-BMED Model Power Meter has 100A CTs
connected to it, the system reactive power (kVAR) is calculated by:
●
Read register 40004.
●
Multiply the value returned from register 40004 by 0.004.
Table 33: VERIS Modbus Floating Point Registers
Modbus
Register
Offset
ViewPoint Name
Description
40257
256
VERIS Float kWh System MSW
System Net True Energy (kWh, Resettable)
40258
257
VERIS Float kWh System LSW
System Net True Energy (kWh, Resettable)
40261
260
VERIS Float kW System MSW
System Total True Power MSW
40262
261
VERIS Float kW System LSW
System Total True Power LSW
40263
262
VERIS Float kVAR System MSW
System Total Reactive Power MSW
40264
263
VERIS Float kVAR System LSW
System Total Reactive Power LSW
40265
264
VERIS Float kVA System MSW
System Total Apparent Power MSW
40266
265
VERIS Float kVA System LSW
System Total Apparent Power LSW
40267
266
VERIS Float PF System MSW
System Total Power Factor MSW
40268
267
VERIS Float PF System LSW
System Total Power Factor LSW
40269
268
VERIS Float Volts Line to Line Avg MSW
Voltage Line to Line Average MSW
40270
269
VERIS Float Volts Line to Line Avg LSW
Voltage Line to Line Average LSW
40271
270
VERIS Float Volts Line to Neutral Avg MSW
Voltage Line to Neutral Average MSW
40272
271
VERIS Float Volts Line to Neutral Avg LSW
Voltage Line to Neutral Average LSW
40273
272
VERIS Float Amps System Avg MSW
Total Current in all Phases MSW
40274
273
VERIS Float Amps System Avg LSW
Total Current in all Phases LSW
40275
274
VERIS Float kW L1 MSW
Individual Phase True Power L1 MSW
40276
275
VERIS Float kW L1 LSW
Individual Phase True Power L1 LSW
40277
276
VERIS Float kW L2 MSW
Individual Phase True Power L2 MSW
40278
277
VERIS Float kW L2 LSW
Individual Phase True Power L2 LSW
40279
278
VERIS Float kW L3 MSW
Individual Phase True Power L3 MSW
40280
279
VERIS Float kW L3 LSW
Individual Phase True Power L3 LSW
40281
280
VERIS Float Apparent PF L1 MSW
Individual Phase Apparent Power Factor L1 MSW
40282
281
VERIS Float Apparent PF L1 LSW
Individual Phase Apparent Power Factor L1 LSW
40283
282
VERIS Float Apparent PF L2 MSW
Individual Phase Apparent Power Factor L2 MSW
40284
283
VERIS Float Apparent PF L2 LSW
Individual Phase Apparent Power Factor L2 LSW