Frequently Asked Questions - FAQs
119
Building Technologies
125-202
06/06/2017
See
Prepping for Field Installation.
How can I fix BACnet network timing errors/slowness?
The maximum number of the MSTP master should be set to the highest MAC address
present in the network. Max Master is a setting on the Communications tab of the
ViewPoint™ software.
What is the purpose of setting a scalar value?
Each Modbus register is only 16 bits wide and is in integer format without any fixed
number of decimal points. Simply putting a value directly into one of these registers
would limit the smallest number to 1, and only allow for a maximum value of 65535. To
handle larger numbers, or numbers with better resolution, we use a scalar value to
apply a factor in multiples of 10 to the 16 bit data register value.
How do I update the firmware in BACnet mode?
If you are not using a USB connection, the Power Meter must be in Modbus mode in
order to use ViewPoint to update the firmware (either through the software switch or
the rotary switches). See
Appendix E.