Installation
Wiring Connections on the MD-BMS and MD-BMED Power Meters
41
Building Technologies
125-202
06/06/2017
Wiring Connections on the MD-BMS and MD-BMED Power
Meters
NOTE:
All wiring added must be rated for 600V CAT III applications.
WARNING
High voltage may be present. Risk of electric shock. Life threatening voltages may be
present. Qualified personnel only.
Haute tension peut être présente. Risque de choc électrique. Tensions dangereuses
peuvent être présentes. Personnel qualifié uniquement.Consequences
The MD-BMS and MD-BMED Power Meters have the following wiring connections:
●
(Optional) USB port for powering the meter and communicating during setup, a
three-wire connector for the RS-485 BACnet/Modbus link, and an Ethernet port.
●
Digital pulse output port. The port can be used to output kWh, kVARh, or kVAh
pulses to external devices, or to toggle on and off to control a remote device or
relay.
●
Three CT inputs.
●
Four voltage connections. Voltage leads are customer supplied. MD-BMS or MD-
BMED meters are self-powered from L1 and L2.
●
A dedicated circuit breaker or fuses is recommended to be installed between the
mains voltages being measured and the red voltage inputs to the meter. See
Part
Number 567-090-01, Fuse Module as an acceptable solution.