Appendices
Appendix B - MD-BMS and MD-BMED Power Meters Modbus Absolute/Net Value Measurement Registers and
Protocol Commands
83
Building Technologies
125-202
06/06/2017
Modbus
Offset
Register
Description
46080
6079
Positive kW System Average
Equals Positive KWH_SYSTEM_L&M ÷
(TimeSinceReset_L&M seconds /3600
seconds/Hr) (resettable).
46081
6080
Positive kW Demand System
Minimum
Minimum Average power window (kW)
46082
6081
kVA Demand System Maximum
Maximum Instantaneous kVA Demand (kW,
resettable).
46083
6082
kVA Demand System Now
System Average kVA Demand for the most recent
(current) Demand Window (resettable).
46084
6083
kVAR Demand System Max
System Maximum kVAR Demand (kVAR,
resettable). It displays the default value after a
CAM until one demand window elapses. After a
power cycle or CPU reset, the value is not reset
and does not update again until one demand
window elapses.
Table 22: Negative Power/Energy Measurement Registers.
Modbus
Offset
Register
Description
47001
7000
Negative kWh System LSW
System Negative True Energy LSW (kWh,
resettable)
47002
7001
Negative kWh System MSW
System Negative True Energy MSW (kWh,
resettable)
47003
7002
Negative kW System
System Negative Instantaneous Negative True
Power (kW) (net sum of all individual kWs, if
sum is positive value = 0).
47004
7003
kW Demand System Max
System Maximum Demand (peak demand).
47005
7004
kW Demand System Now
Average Power (kW) for most recent demand
window
47006
7005
Negative kW System Max
System Net Highest Instantaneous Negative
Draw Since Reset (kW, resettable)
47007
7006
Negative kW System Min
System Net Lowest Instantaneous Negative
Draw Since Reset (kW, resettable)
47008
7007
Negative kVARh System LSW
System Net Negative Reactive Energy LSW
(kVARh, resettable)
47009
7008
Negative kVARh System MSW
System Net Negative Reactive Energy MSW
(kVARh, resettable)
47010
7009
Negative kVAR System
System Net Instantaneous Negative Reactive
Power (kVAR) (net sum of all individual kVARs,
if sum is positive value = 0)
47011
7010
kVAh System LSW
System Apparent Energy LSW (kVAh,
resettable)
47012
7011
kVAh System MSW
System Apparent Energy MSW (kVAh,
resettable)