Introduction
Maintenance
15
Building Technologies
125-202
06/06/2017
Communication
RS 485 Transceiver unit load
size Loading
1/8 Load unit
Data Formats
BACnet Master Slave/Token Passing (MS/TP) protocol (default) or
Modbus RTU protocol.
The MD-BMED Model adds Ethernet with BACnet IP or Modbus TCP.
Mechanical
Operating Temperature
-20°F to 140°F (-7°C to 60°C)
Humidity
5% to 95% non-condensing
Enclosure
ABS plastic, 94-V0 flammability rating
Weight
12 ounces (340 g), exclusive of CTs
Dimensions
9.5” × 3. 3” × 1.6” (24.2 × 8.5 × 4.0 cm)
Ingress Protection
IP 20
Accessories
Mounting Rail
Compatible with a TS35/7 DIN Rail Channel
Digital Display
An optional 2 × 16 character display which auto-cycles between
informational screens every 2-3 seconds, with real-time values updated
every second.
ViewPoint Minimum System Requirements
Operating System
Windows® 7(32 or 64 bit), Windows® 8 Pro, Vista (32 or 64 bit), XP,
Windows® 10 (32 or 64 bit).
Communications Port
One USB port and Type AB cable
Hard Drive
50 MB minimum available
Processor
Pentium Class 1 GHz or more recommended
Safety
Regulatory Agencies
UL Listed to UL Standard 61010-1
●
IEC 61010-2-030
●
cUL certified to CAN/CSA Standard
●
C22.2 No. 61010-1
●
Certified to CSA Std. C22.2, No. 61010-1
FCC Part 15, Class B
RCM (formerly C-Tick)
RoHS Compliant
WEEE Compliant
BACnet Testing Labs certified smart sensor (B-SS) device