Appendices
Appendix B - MD-BMS and MD-BMED Power Meters Modbus Absolute/Net Value Measurement Registers and
Protocol Commands
75
Building Technologies
125-202
06/06/2017
Modbus
Offset
Register
Description
44020
4019
Volts L2 to L3
Individual Phase to Phase Voltage
44021
4020
Volts L1 to L3
"
44022
4021
Line Frequency
Line Frequency (Hz)
44023
4022
kWh L1 LSW
Individual Phase True Energy LSW (kWh)
44024
4023
kWh L1 MSW
Individual Phase True Energy MSW (kWh)
44025
4024
kWh L2 LSW
"
44026
4025
kWh L2 MSW
"
44027
4026
kWh L3 LSW
"
44028
4027
kWh L3 MSW
"
44029
4028
kW L1
Individual Phase True Powers (kW)
44030
4029
kW L2
"
44031
4030
kW L3
"
44032
4031
kVARh L1 LSW
Individual Phase Reactive Energy LSW (kVARh)
44033
4032
kVARh L1 MSW
Individual Phase Reactive Energy MSW (kVARh)
44034
4033
kVARh L2 LSW
"
44035
4034
kVARh L2 MSW
"
44036
4035
kVARh L3 LSW
"
44037
4036
kVARh L3 MSW
"
44038
4037
kVAR L1
Individual Phase Reactive Powers (kVAR)
44039
4038
kVAR L2
"
44040
4039
kVAR L3
"
44041
4040
kVAh L1 LSW
Individual Phase Apparent Energy LSW (kVAh)
44042
4041
kVAh L1 MSW
Individual Phase Apparent Energy MSW (kVAh)
44043
4042
kVAh L2 LSW
"
44044
4043
kVAh L2 MSW
"
44045
4044
kVAh L3 LSW
"
44046
4045
kVAh L3 MSW
"
44047
4046
kVA L1
Individual Phase Apparent Powers (kVA)
44048
4047
kVA L2
"Individual Phase Apparent Powers
44049
4048
kVA L3
"
44050
4049
Displacement PF L1
Individual Phase displacement Power Factor (PF)