Installation
Wiring CTs
49
Building Technologies
125-202
06/06/2017
1. Connect the white wire on the CT to the positive terminal on the measuring device.
2. Connect the black wire on the CT to the negative terminal on the measuring
device.
NOTE:
Correct orientation of a CT is required to ensure proper measurement. If an arrow is
shown on the CT label, it should be pointed toward the load. Otherwise, use the
instructions printed on the CT.
Connecting Rogowski Coil CTs to a Load
To install a Rogowski Coil CT to the conductor(s):
NOTE:
See
Connecting a Rogowski Coil Flexible Current Transformer to a Load Installation
Instructions (129-554) for detailed instructions.
1. Open the CT by squeezing the connector latch and pulling it apart.
2. Connect the CT around the load conductor to be measured. Orient the CT so that
the arrow on the CT case points towards the load. Ensure the maximum current of
the conductor does not exceed 5,000 amps.
3. Push the connector back together with the conductor within the loop of the CT.