Prepping for Installation
Establishing Communication Protocol
38
Building Technologies
125-202
06/06/2017
4. In the Value field, enter 1833 to change to BACnet mode.
5. Click OK.
The status should read:
Writing Value…
●
Return to the Communications tab and Connect.
Changing the MD-BMS or MD-BMED Power Meter from
BACnet to Modbus Mode
1. Connect to the MD-BMS and MD-BMED using ViewPoint.
2. Go to the Read/Set Objects tab in ViewPoint.
3. Enter 10190 into the Object field or click List to select from the Object Picker list.
4. In the Value field, enter 375 to change to Modbus mode.
5. Click OK.
The status should read:
Writing Value…
●
Return to the Communications tab and Connect.