Appendices
Appendix A - MD-BMS and MD-BMED Power Meters BACnet Analog Value Objects
71
Building Technologies
125-202
06/06/2017
Pulse Output/Input Objects
Object
Identifier
Name
Description
13020
Port 1 output control when used as an on/off-
open/closed switch
0 = Output LOW (closed)
1 = Output HIGH (open) [default]
Object 13100 present value must = 0 to use.
13100
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on’/off-
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13110
Port 1 pulse output relay type
0 = Normally open (HIGH)
1 = Normally closed (LOW)
14014
BBMD IP Address
LSW object identifier
14015
BBMD IP Address
MSW object identifier
Device Status Objects
Object
Identifier
Name
Description
10080
Hardware ID
Hardware revisions
10090
Features
New features
10130
Reset Processor
Processor reset
10150
MD Model Power Meter Element
ID
Used for ViewPoint to determine which element is
being read and total number of elements available.
Element index multiplied by 256 + number of elements.
Positive Power/Energy Accumulator Objects
Object
Identifier
Name
Description
1080
kW System Average Positive
Equals kWh System Positive/(Time Since Reset/3600
seconds/Hr) (resettable) (Signed Net)
1110
kW System Maximum Positive
System Highest Instantaneous Positive Draw Since Reset
(kW) (Signed Net)
1140
kW System Minimum Positive
System Lowest Instantaneous Positive Draw Since Reset
(kW, resettable)
2010
kWh System Total Positive
System True Energy (kWh) Positive (Signed Net)
2040
kWh L1 Positive
Individual Phase True Energy (kWh) (Signed)
2070
kWh L2 Positive
"